Pressure test pressure and hold time

A pressure test proves strength and tightness at a pressure above the design pressure, and every construction code sets its own multiplier. The differences are not cosmetic. ASME BPVC Section VIII Division 1 requires 1.3 × MAWP for a hydrostatic test (it was 1.5 before the 1999 Addenda — always check the edition the item was built to), Division 2 requires 1.43 × MAWP, ASME B31.3 and B31.1 require 1.5 × design pressure for piping, and pneumatic tests sit much lower at 1.1 × MAWP for VIII-1 and B31.3 because of the stored energy involved.

The second factor is temperature. Allowable stress falls as design temperature rises, so a vessel designed for a hot service is tested cold with extra pressure to reach the same fraction of allowable stress: the multiplier is scaled by the stress ratio S_test/S_design, the ratio of allowable stress at test temperature to allowable stress at design temperature, both read from the code stress tables for the actual material. ASME VIII-1 caps that ratio at 6.5. The ratio never reduces the test pressure below the basic multiplier — where S_test/S_design is less than 1, use 1.

Hold time is where technicians are most often let down by memory. ASME B31.3 and B31.1 both require the test pressure to be held at least 10 minutes before examination; ASME VIII-1 UG-99 sets no numeric hold, leaving it to the design or the job specification, and common practice is 30 minutes. Examination pressure differs too: VIII-1 UG-99(g) allows the visual examination to be made after reducing to the test pressure divided by 1.3, while B31.3 345.2.2(b) requires the pressure to be reduced to the design pressure before the joints are examined.

Two things this arithmetic will not do for you. It will not confirm that the item, in its current corroded condition, can take the test pressure — that is a fitness-for-service calculation on measured thickness. And it will not make a pneumatic test safe: stored energy in compressed gas is orders of magnitude higher than in water, and pneumatic testing needs an exclusion zone, a documented risk assessment and a code-recognised justification for not using liquid.

Worked example

Governing code and test typeb313_hydro
Design pressure / MAWP10 bar
Stress ratio S_test / S_design1.2
Planned hold time30 min
Code multiplier1.5
Stress ratio applied1.2
Required test pressure18 bar
Test / design pressure1.8
Code minimum hold time10 min
Hold time to apply30 min
Static head of the test water column0 bar
Gauge reading required at that elevation18 bar

ASME B31.3 345.4.2 gives 1.5 x design pressure, scaled by the stress ratio: 1.5 x 10 x 1.2 = 18.00 bar, which is 1.8 times the design pressure. The code minimum hold is 10 minutes; the planned 30 minutes governs. With the gauge at the system high point (0 m of column) there is no head to add, so the gauge reads the 18.00 bar test pressure directly.

Use at your own risk — verify before you act

These calculators support, and never replace, the judgement of qualified NDT and engineering personnel. Results are provided as is, without warranty of any kind, express or implied, and must be independently verified against the governing code edition named in your contract before being used in any inspection, acceptance, rejection, radiation-safety or fitness-for-service decision. By using them you accept full responsibility for how the results are applied; NDT Inspect, its owners and contributors accept no liability for any loss, damage, injury or death arising from their use or from reliance on them. If a result matters to safety, check it by hand and have it reviewed by a competent person.

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.