Coil shot current, low fill factor
A coil (encircling) shot drives a longitudinal field along the axis of the part, so it reveals discontinuities lying transverse to that axis. What sets the field inside the coil is the magnetomotive force, the ampere-turns NI – current multiplied by number of turns – not the current alone. A five-turn coil at 1 000 A and a one-turn wrap at 5 000 A produce the same field.
The part fights back. Its own end poles create a demagnetising field that opposes the applied field, and that opposing field grows as the part gets shorter and fatter. The empirical codes capture this with the length-to-diameter ratio L/D: required ampere-turns fall as L/D rises. Below L/D = 2 the demagnetising field dominates and the formula stops being meaningful; above L/D = 15 there is no further gain, so 15 is the value used.
Low fill factor means the coil is much larger than the part – the coil bore cross-section is at least ten times the part cross-section. The part sits far from the windings, out where the field has spread and weakened, so it needs more ampere-turns than a snug coil would. For the same reason the part is normally laid against the inside wall of the coil, where the flux is concentrated, and the wall-position formula NI = 45 000/(L/D) applies. Where the part must instead hang centred on the coil axis – on a fixture, or from a crane sling – the standards give a different relation, NI = 43 000 R / (6 L/D - 5) with R the coil radius in inches: out on the axis the field the part sees depends on the size of the coil itself, so the coil radius enters the calculation.
The result is a starting point, not a guarantee. A coil’s field is only usefully strong for roughly 230 mm (9 in.) either side of it, so long parts need several overlapping shots. Confirm the actual tangential field at the surface with a Hall-effect gaussmeter (30-60 G) or with artificial flaw shims before accepting the technique.
Worked example
| Part length | 300 mm |
| Part diameter | 50 mm |
| Part position in the coil | wall |
| Coil inside diameter | 300 mm |
| Coil turns | 5 |
| L/D used | 6 |
| Required ampere-turns | 7500 A-turn |
| Ampere-turns, -10% | 6750 A-turn |
| Ampere-turns, +10% | 8250 A-turn |
| Coil current | 1500 A |
| Current, lower tolerance | 1350 A |
| Current, upper tolerance | 1650 A |
| Coil positions needed | 1 |
A 300 mm long, 50 mm diameter shaft laid against the wall of a large 5-turn coil. L/D = 300/50 = 6, inside the valid 2 to 15 band. NI = 45 000/6 = 7 500 ampere-turns; the ±10% band is 6 750 to 8 250. With 5 turns the machine is set to 7 500/5 = 1 500 A, tolerance 1 350 to 1 650 A. The part is shorter than 2 x 230 = 460 mm, so one coil position covers it. Suspended in the centre of a 300 mm bore coil instead, the requirement would rise to NI = 43 000 x (150/25.4)/(6 x 6 - 5) = 43 000 x 5.906/31 = 8 192 ampere-turns, about 1 638 A on the same 5 turns.
Use at your own risk — verify before you act
These calculators support, and never replace, the judgement of qualified NDT and engineering personnel. Results are provided as is, without warranty of any kind, express or implied, and must be independently verified against the governing code edition named in your contract before being used in any inspection, acceptance, rejection, radiation-safety or fitness-for-service decision. By using them you accept full responsibility for how the results are applied; NDT Inspect, its owners and contributors accept no liability for any loss, damage, injury or death arising from their use or from reliance on them. If a result matters to safety, check it by hand and have it reviewed by a competent person.