High temperature thickness correction
Sound travels more slowly in hot steel. The elastic moduli soften as temperature rises while the density barely changes, and the compression velocity falls by roughly 1 % for every 55 °C (100 °F) above the temperature at which the instrument was calibrated. A gauge calibrated cold and then applied to a hot line is still converting time to distance with the cold velocity, so every reading comes out high — the wall looks thicker than it is, which is the dangerous direction for a corrosion survey.
The correction is a simple ratio. The true thickness is the displayed thickness scaled by the ratio of hot velocity to calibration velocity, t = t_disp × (1 − k ΔT). At 350 °C the factor is about 0.94, so a 12.70 mm reading is really 11.94 mm — three-quarters of a millimetre, which on a line with a 0.15 mm/yr corrosion rate is five years of remaining life.
Temperature affects more than velocity. The couplant must survive the surface, the probe itself has a duty-cycle limit and its delay line changes velocity as it heats, and the steel has physically expanded — around 0.4 % at 350 °C — so the hot wall is genuinely thicker than the same wall cold. This calculator corrects the velocity error only; where readings are being trended against a cold minimum thickness, the thermal expansion should be considered separately.
The cleanest way to avoid the whole problem is to calibrate on a block at the operating temperature, or on the component itself against a known thickness. Where that is impossible, apply the correction and record on the report that it was applied, at what metal temperature, and with what coefficient.
ΔT = T_metal − T_calibration correction factor k_f = 1 − k · ΔT t_corrected = t_displayed × k_f k = 0.00018182 /°C for steel (1 % per 55 °C, i.e. 1 % per 100 °F) c at temperature = c_calibration × k_f
- The 1 % per 55 °C figure is a linear approximation used across the petrochemical industry; verify it on a heated block where the readings drive a fitness-for-service decision.
- Calibrating on a block held at the operating temperature removes the need for the correction entirely and is the preferred method.
- High-temperature couplant, a delay-line probe and a strict duty cycle are required above roughly 100 °C; a hot delay line also drifts in velocity and must be re-zeroed as it warms.
- Steel expands about 0.4 % at 350 °C, so the hot wall is physically thicker than the same wall cold. This correction addresses velocity only.
Reference: API RP 574 (Inspection Practices for Piping System Components) — reduce readings approximately 1 % per 100 °F (55 °C) above calibration temperature; ASTM E797


